How to apply logical rules to a sluice or gated weir
    • 10 Jul 2023
    • 1 Minute to read
    • Dark
      Light

    How to apply logical rules to a sluice or gated weir

    • Dark
      Light

    Article Summary

    Logical rules can be added to a vertical sluice, radial sluice, or gated weir, to enable their control to be determined by specified situations.

    This could include specifying the gate to open based on the water level at a given reference point, for instance.

    Note:

    This guide covers the minimum data required. Several optional settings are also available for logical rules, please see the Rules section of the technical reference for further details.

    Steps

    1. Open the vertical sluice, radial sluice, or gated weir unit to which you are applying the rule(s) and navigate to the Control Data tab.

    2. Use the drop-down to change the Control Method to LOGICAL. Add values in the fields provided for the Minimum Setting, Maximum Setting and Max Movement Rate of the gate. In the table provided, set the Mode to AUTO to use automatic mode from the start (time 0). When in automatic mode the unit will be driven by the rules you define.

    3. Navigate to the Rules sub-tab to add your logical rules. Click New Rule and the Rule editor will open in a new window. The rule must be of the form:

      IF (xxx)

      THEN MOVE = () or THEN POSITION = ()

      END

      Where xxx is a logical statement that can be evaluated as true or false. An example is provided below.

    4. Repeat step 3 as required. Following 1 or more of the IF rules, an ELSE condition can be optionally provided to cover all other eventualities:

      ELSE MOVE = () or ELSE POSITION = ()

      END

      An ELSE rule must be located as the final rule in the list. 

      Example usage: controlling the gate opening of a sluice according to the water level at the gauge point A2.

      • Rule1 opens gate by 0.1 (metres) when the water level at A2 is between 12.2m and 13.0m
      • Rule2 sets the gate position to 1.0 (metres) when the water level at A2 is 13.0m or higher
      • Rule3 sets the gate position to 0.0 (metres) in other situations (i.e. when the water level at A2 is 12.2m or lower)

      RULE1

      IF(LEVEL(A2).GT.12.2.AND.LEVEL(A2).LT.13.0)

      THEN MOVE=0.1

      END

      RULE2

      IF(LEVEL(A2).GE.13.0)

      THEN POSITION=1.0

      END

      RULE3

      ELSE POSITION=0.0

      END

      Note:

      RULE3 above could also be achieved with the condition IF(LEVEL(A2).LE.12.2)

    5. Click OK to save and close the unit. Don't forget to also Save these changes to the network.

    Note:

    Each rule can provide a maximum of one action to be applied to the unit (gate, in this case), however ALSO statements can be added to define rules for global variables

    You can also apply logical rules to a pump and apply logical rules to an abstraction unit.


    Was this article helpful?

    Changing your password will log you out immediately. Use the new password to log back in.
    First name must have atleast 2 characters. Numbers and special characters are not allowed.
    Last name must have atleast 1 characters. Numbers and special characters are not allowed.
    Enter a valid email
    Enter a valid password
    Your profile has been successfully updated.